M-vintage twin/quad circuit vertical water source heat pumps are floor-mounted in closets or small mechanical rooms near the occupied space. These units offer the opportunity to serve larger spaces with a single unit. Mammoth offers some of the quietest water source heat pump units in the industry, allowing units to be located near the occupied space with minimal acoustic impact.
Basic Features and Benefits:
For more information, contact your local representative.
Unit Size
CFM
GPM
M Vintage Vertical - Water Loop (Boiler/Tower)1
Cooling
Heating
Qt
Qs
kW
EER
COP
084VHM
2800
22
83,900
69,000
5.7
14.8
96,200
5.8
4.8
096VHM
3200
26
96,800
78,800
6.5
15.0
113,100
7.0
4.7
120VHM
4000
32
124,900
100,200
8.5
14.7
141,600
9.2
4.5
144VHM
4400
35
138,800
110,300
9.8
14.2
157,400
10.7
4.3
168VHM
5600
44
167,800
138,000
11.4
192,300
11.6
192VHM
6400
52
193,500
157,500
12.9
226,200
14.1
240VHM
8000
64
249,900
200,300
17.0
283,300
18.5
288VHM
8800
70
277,600
220,600
19.6
314,900
21.4
1 Rated in accordance with ISO 13256-1 – Boiler/Tower. Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 86°F (30°C) entering water temperature. Heating capacity is based on 68°F (20°C) entering air temperature and 68°F (20°C) entering water temperature. For exact dimensional data, contact your local representative for a selection.
M Vintage Vertical - Ground Loop (Geothermal)1
084VLM
82,900
66,900
14.5
55,800
5.28
3.1
096VLM
95,700
76,800
6.49
65,600
6.39
3.0
120VLM
123,500
97,600
8.55
14.4
82,100
8.39
2.9
144VLM
137,200
108,000
9.83
14.0
91,300
9.71
2.8
168VLM
165,800
133,800
11.42
111,500
10.56
192VLM
191,300
153,600
12.99
131,200
12.80
240VLM
247,000
195,300
17.09
164,300
16.78
288VLM
274,400
215,900
19.66
182,600
19.42
1 Rated in accordance with ISO 13256-1 – Ground Loop. Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 77°F (25°C) entering water temperature. Heating capacity is based on 68°F (20°C) entering air temperature and 32°F (0°C) entering water temperature. For exact dimensional data, contact your local representative for a selection.